I. Overall Structure Composition


The electric actuator is powered by an AC or DC motor, integrating a reduction transmission mechanism, position feedback component, control circuit board, stroke limit mechanism, manual operation module, and is equipped with a valve stem connection output shaft. It is matched with various valves to convert electrical energy into linear mechanical motion or angular stroke rotation, achieving the opening, closing, and opening degree adjustment of the valve.


II. Basic Principle of Power Drive


The control system receives external switch quantity or analog quantity control signals, which are converted and processed by the main control circuit board to output a power supply current to drive the motor to operate; the motor outputs high-speed, low-torque power, which is reduced in speed and amplified in output torque by multi-stage gears, worm gears, and worm wheel worm gears to drive the actuator output shaft to generate stable mechanical driving force, thereby driving the valve stem to move and change the valve's on-off state or flow opening degree.


III. Principle of Stroke Limiting and Shutdown Control


The actuator is equipped with a dual protection structure of mechanical limit and electrical limit. When the output shaft rotates to the preset positions of full open or full close of the valve, the mechanical stop block limits the physical stroke, and simultaneously triggers the internal microswitch, cutting off the motor power supply circuit, causing the motor to stop running, preventing the valve from over-stroke and crushing the valve seat or transmission components. Some adjustable-type actuators can precisely set any intermediate stop position through electronic limit.


IV. Position Feedback and Closed-loop Regulation Principle


The adjustable-type electric actuator is equipped with a potentiometer or Hall-type position sensor. The sensor collects the rotational angle of the output shaft in real time and converts it into corresponding resistance, voltage, or standard current feedback signals and transmits them back to the control loop. The controller compares the feedback signal with the external given control signal. If there is a difference, it continuously drives the motor to run in the forward or reverse direction; when the feedback value is consistent with the given value, the motor is de-energized and stops, maintaining the target opening degree stably, forming a closed-loop automatic regulation.


V. Manual Emergency Operation Principle


In the event of power failure or electrical control system failure, the clutch mechanism can be switched to disengage the motor reduction transmission link, and directly drive the output shaft to rotate through the matching handwheel, completing the valve opening and closing operation manually; after power is restored, the clutch structure automatically resets, and re-enters the motor-driven transmission system.


VI. Protection Control Logic


The control board integrates overload, overheating, and phase failure protection functions. When the valve gets stuck, causing the motor load to exceed the standard, the coil temperature to rise abnormally, or the power supply power phase failure, the protection circuit immediately cuts off the motor power supply, locks the output action, and avoids structural damage such as motor burnout or transmission gear fracture; after the fault is eliminated, it can re-accept the control signal to resume operation.


VII. Signal Control Classification Work Logic


Switch-type Electric Actuator


It only receives two independent switch signals for opening and closing, and when the signal is connected, the motor runs in a single direction, stops automatically when reaching the limit, and can only achieve two-position actions of full open and full close, unable to maintain an intermediate opening degree.


Adjustable-type Electric Actuator


It receives 4-20mA, 0-10V, etc., continuous analog control signals, based on the corresponding 0% to 100% valve opening degree of the signal value, relying on the position closed-loop to continuously correct the output shaft angle, can precisely and stably maintain any intermediate opening degree, and achieve continuous regulation of pipeline flow and pressure.